To test the insulation resistance to DIN VDE 0100 Part 610 and the characteristic curve behaviour of the following surge voltage and lightning current arrestors:
? V10-C and V20-C: Uc Tolerance range
75 V -> 110 V - 130 V
150 V -> 215 V - 265 V
280 V -> 385 V - 475 V
320 V -> 460 V - 560 V
335 V -> 460 V - 560 V
385 V -> 560 V - 680 V
440 V -> 645 V - 785 V
550 V -> 820 V - 1,000 V
? V25-B+C and V50-B+C: Uc Tolerance range
150 V -> 215 V - 265 V
280 V -> 385 V - 475 V
320 V -> 460 V - 560 V
385 V -> 560 V - 680 V
? Varistor arrestors of other manufacturers can be tested for 1 or 3 mA characteristic curve behaviour
? Battery operation
? Measuring cables contained in the scope of delivery.
| Type | Country-specific version |
Nominal voltage V |
Measuring range |
Pack. pcs |
Weight kg/100 pcs. |
Art.-No. | Add to item list |
| ISOLAB | D/GB | 6 | 0 V - 999 V | 1 | 165.000 | 5096812 |
|
| /pc. |
Download Datasheet (PDF)