Halogen-free junction box, approved for electrical function maintenanceaccording to DIN 4102 Part 12. Function maintenance classes E30 to E90Including premounted connection unit made of high temperature-resistant special ceramic and labelled protective conductor terminal. Supplied with fire protection screw ties for anchorless fastening.Power cable nominal cross-sections: 1.5 to 4 mm2, data cables with 0.8 mm wire ?. Maximum of 2 1.5 mm2 rigid copper cables per terminal (remove wire protection).High protection rating IP65, impact resistance class IK07. VDE-tested.Details on the cable types and manufacturers can be found in the general construction test certificate of the material testing institute MPA NRW, Erwitte.Number of terminals including protective conductor terminalInternal clearance: 136 x 102 x 57?mm
Download Datasheet (PDF)